Danfoss ERC112D Programming Instruction

थांबवा! All work detailed in these instructions must be done by a qualified technician.

तपशील

  • विषय: Danfoss ERC112D Universal Programming Instructions
  • तारीख: २८ फेब्रुवारी २०२४
  • मॉडेल्स / प्रभावित भाग: Temperature Control Kit P#848288
  • खंडtages: सर्व खंडtages

ओव्हरview

  • Universal Danfoss ERC112D Temperature control kit contains all components potentially required for repairing a temperature control failure. Use of components will vary by repair.
  • The replacement control is preprogrammed for universal use and may require changes to parameter settings based on model type and application.
  • Some component operations may change with new universal settings.

CVM/GDM/TCR/TD/TMC/TUC/TWT REFRIGERATORS ONLY: No programming changes required.

इतर सूचना
Follow the links/QR codes for digital copies of instructions associated with this kit.true-ERC112D-Temperature-Control-Kit-image (1)

आपण सुरू करण्यापूर्वी

If adjusting the set point to 41°F (5°C) or greater, place the provided hazardous food warning label below the serial label inside the appliance as shown in fig. 1. This label notifies users the appliance has been set to maintain a temperature above outside NSF perishable food storage guidelines. true-ERC112D-Temperature-Control-Kit-image (2)

स्थापना

TOAM-72 ONLY: Verify the third defrost probe’s operation. If operating correctly reuse the probe. If operating incorrectly, please see “TOAM-72 Only — Third Defrost Probe” section (pg. 4).

  • सावधान! Electrical shock or burn hazard. Powering off an electronic control does not remove power from all components. Unplug the unit or turn off the power supply before installation.
  • खबरदारी! Sharp edges. Take care when installing, cleaning, servicing, and/or maintaining the equipment.true-ERC112D-Temperature-Control-Kit-image (3)

Control Program Structure

  • Parameters are arranged in parameter groups according to their purpose (see fig. 2a). For example, all fan operations are found within the FAn parameter group (see fig. 2b).
  • For more information on navigating the control programming, please see “Adjust Parameters” section.true-ERC112D-Temperature-Control-Kit-image (4)

Unlock Control

  1. Press any button to show the current lock status.true-ERC112D-Temperature-Control-Kit-image (5)
  2. If the display shows unL, proceed to “Enter Password” section. If the display shows Loc, press and hold the back button true-ERC112D-Temperature-Control-Kit-image (6)and the up arrow true-ERC112D-Temperature-Control-Kit-image (7)until the display shows unL.
    टीप: The control will lock after 60 seconds of inactivity.
    true-ERC112D-Temperature-Control-Kit-image (7)
  3. Proceed to “Change System of Measure,” “Enter Password,” or “Adjust the Set Point” sections.

Change System of Measure
डिस्प्ले फॅरेनहाइट किंवा सेल्सिअसमध्ये तापमान दर्शवू शकतो.

  1. Unlock the display. See “Unlock Control” section.
  2. मागील बटण दाबाtrue-ERC112D-Temperature-Control-Kit-image (6)true-ERC112D-Temperature-Control-Kit-image (7)

पासवर्ड टाका

टीप: After three (3) consecutive incorrect password entries, the control will lock for 15 minutes.

  1. Push and hold both the uptrue-ERC112D-Temperature-Control-Kit-image (10) arrows until the  display shows PAS.true-ERC112D-Temperature-Control-Kit-image (11)
  2. डिस्प्ले ० दिसेपर्यंत वाट पहा. true-ERC112D-Temperature-Control-Kit-image (12)
  3. Press the down arrow until the display shows 989.true-ERC112D-Temperature-Control-Kit-image (13)
  4. Press okaytrue-ERC112D-Temperature-Control-Kit-image (14) to show PS2.true-ERC112D-Temperature-Control-Kit-image (15)
  5. Wait for the display to show tHE.true-ERC112D-Temperature-Control-Kit-image (16)
  6. Proceed to “Adjust Parameters” or “Adjust the Set Point” sections.

Danfoss ERC112D Programming Instruction

true-ERC112D-Temperature-Control-Kit-image (17)

पॅरामीटर्स समायोजित करा

  • See table 1 (next page) for required parameter adjustments before proceeding.
  • The figures show how to, in the parameter group FAn, change the parameter FCt to the parameter setting FAo (also shown in fig. 3). This setting change may not be required for your application.
    टीप: Incorrect parameter settings can lead to improper appliance operation and unsafe product temperatures.
  1. Unlock the control. See “Unlock Control” section.
    टीप: The control will lock after 60 seconds of inactivity.
  2. Enter the password and enter the programming. See “Enter Password” section.true-ERC112D-Temperature-Control-Kit-image (18)
  3. वर दाबा true-ERC112D-Temperature-Control-Kit-image (10) arrow as needed to show the desired parameter group.true-ERC112D-Temperature-Control-Kit-image (19)
  4. Press okaytrue-ERC112D-Temperature-Control-Kit-image (14) to select the parameter group.true-ERC112D-Temperature-Control-Kit-image (20)
  5. Press the up or down arrow as needed to show the desired parameter.true-ERC112D-Temperature-Control-Kit-image (21)
  6. Press okay to select the parameter.true-ERC112D-Temperature-Control-Kit-image (22) true-ERC112D-Temperature-Control-Kit-image (22)
  7. Press the up or down arrow as needed to show the desired parameter setting.true-ERC112D-Temperature-Control-Kit-image (24)
  8. Press okay to select the parameter setting. The display will return to the selected parameter.true-ERC112D-Temperature-Control-Kit-image (25)
  9. मागील बटण दाबाtrue-ERC112D-Temperature-Control-Kit-image (6) to return to the selected parameter group. Repeat steps 3-8 as needed to adjust parameter settings per table 1 (next page).true-ERC112D-Temperature-Control-Kit-image (26)
  10. Exit the programming.
    • Press the back button twice (x2) OR
    • Leave the control inactive for 30 seconds

Parameter Setting Adjustments

  • Table 1 shows how to alter the universal control program to fit your specific model and application.
  • Locate your model type, and then change the parameter settings to the values shown. For instructions on changing parameter settings, see “Adjust Parameters” section.
  • FREEZER MODELS ONLY: Be sure to change duA before adjusting any other parameter setting.

After changing the programming, be sure to adjust the set point for the application per table 2.

TOAM-72 ONLY — Third Defrost Probe

  • Verify the third defrost probe’s operation. If operating correctly reuse the probe.
  • If operating incorrectly, remove a tooth (see fig. 4) from a provided defrost probe.
  • For an additional defrost probe, in the USA or Canada, please contact our parts department at ५७४-५३७-८९०० or PartsInquiries@TrueMfg.com. For all other locations, please see the contact information.true-ERC112D-Temperature-Control-Kit-image (27)
मॉडेल प्रकार Table 1. Required Parameter Setting Changes by Model
पॅरामीटर गट फॅन dEF CoP एएसआय
पॅरामीटर एसपीआर diF duA* एफसीटी dii dAi dit dAt Ftd doC डीईटी dE2 dt2 dSo सीएसटी S3A S4A diC o2C o4C
CPT EuA
CVM
FLM (Freezer)

(1 Cond Unit)

du2 0°F (-17.8°C)
जीडीआयएम du2 12°F (-11.1°C) -10°F (-23.3°C) डीसीओ
GDM (Refrigerator)
GDM (Wine) एफएओ
GDM (Freezer)

(1 Cond Unit)

du2 0°F (-17.8°C) डीसीओ
GDM-LTF

(1 Cond Unit)

du2 0°F (-17.8°C) -40°F (-40°C) डीसीओ
ग्लास चिलर du2 0°F (-17.8°C)
T-Series (Refrigerator) डीसीओ
T-Series (Freezer) (1 Cond Unit) du2 0°F (-17.8°C) डीसीओ
TBR
TBR (Wine) एफएओ
टीसीएफ du2 0°F (-17.8°C) 50°F (10°C)
टीसीजीजी 75 90 180 -13°F (-25°C)
TCR
TD
TDM एफएओ 6
TDM-CW एफएओ 6
टीएफपी 3°F (1.7°C) एफएओ 3 2 5°F (-15°C) 2
TGN (Refrigerator) डीसीओ
TGN (Freezer) du2 0°F (-17.8°C) डीसीओ
थॅक FA0 1 बंद
मॉडेल प्रकार Table 1. Required Parameter Setting Changes by Model
पॅरामीटर गट फॅन dEF CoP एएसआय
पॅरामीटर एसपीआर diF duA* एफसीटी dii dAi dit dAt Ftd doC डीईटी dE2 dt2 dSo सीएसटी S3A S4A diC o2C o4C
टीएमसी
TOAM-30/36 एफएओ 1 बंद
TOAM-48 एफएओ 1 बंद EuA SCC
TOAM-72 एफएओ 1 बंद EuA EuA टीसीसी SCC
TPP 3°F (1.7°C) एफएओ 3 2 5°F (-15°C) 2
टीआरसीबी एफएओ
टीएसएसयू 3°F (1.7°C) एफएओ 3 2 5°F (-15°C) 2
TUC/TWT (Refrigerator)
TUC/TWT (Wine) एफएओ
TUC/TWT (Freezer) du2 0°F (-17.8°C)
TUFADA 1 du2 180 8 0°F (-17.8°C) 240 -25°F (-31.7°C) 6
TURADA 1 180 8 240 9°F (-12.8°C) 6
TUWADA 1 एफएओ 180 8 240 9°F (-12.8°C) 6

Adjust the Set Point (After Programming)

  • Changing the set point adjusts the appliance operation to
  • keep optimal product temperature. See table 2 for factory-recommended temperature set point adjustments based on model.

टीप: Adjust the temperature set point after making programming adjustments.

true-ERC112D-Temperature-Control-Kit-image (28)

टीप: The best set point for your application may vary from the factory-recommended setting.

  1. Unlock the control. See “Unlock Control.”
    टीप: The control will lock after 60 seconds of inactivity.
  2. वर दाबाtrue-ERC112D-Temperature-Control-Kit-image (10) arrow to show the current setting.true-ERC112D-Temperature-Control-Kit-image (29)
  3. Press the up or down arrow until the display shows the desired set point.true-ERC112D-Temperature-Control-Kit-image (30)
  4. Leave the display inactive until it shows the current appliance temperature.

true-ERC112D-Temperature-Control-Kit-image (31)

टेबल 2. Factory-Recommended तापमान सेट बिंदू
मॉडेल संच बिंदू
CPT No further changes required
CVM No further changes required
FLM (Freezer)

(1 Cond Unit)

No further changes required
जीडीआयएम 18°F (-7.8°C)
GDM (Refrigerator) No further changes required
GDM (Red Wine) 55°F (12.8°C)
GDM (White Wine) 45°F (7.2°C)
GDM (Freezer)

(1 Cond Unit)

No further changes required
GDM-LTF

(1 Cond Unit)

-15°F (-26.1°C)
ग्लास चिलर 4°F (-15.5°C)
T-Series (Refrigerator) No further changes required
T-Series (Freezer) (1 Cond Unit) No further changes required
TBR 34°F (1.1°C)
TBR (Red Wine) 55°F (12.8°C)
TBR (White Wine) 45°F (7.2°C)
टीसीएफ No further changes required
टीसीजीजी No further changes required
TCR No further changes required
TD No further changes required
TDM 38°F (3.3°C)
TDM-CW 55°F (12.8°C)
टीएफपी 34°F (1.1°C)
टीजीएन No further changes required
थॅक 38°F (3.3°C)
टीएमसी No further changes required
टॉम 38°F (3.3°C)
TPP 34°F (1.1°C)
टीआरसीबी No further changes required
टीएसएसयू 34°F (1.1°C)
TUC/TWT (Refrigerator) No further changes required
टेबल 2. Factory-Recommended तापमान सेट बिंदू
मॉडेल संच बिंदू
TUC/TWT (Red Wine) 55°F (12.8°C)
TUC/TWT (White Wine) 45°F (7.2°C)
TUC/TWT (Freezer) No further changes required
TUFADA No further changes required
TURADA No further changes required
TUWADA 55°F (12.8°C)

प्रश्न किंवा चिंता
अधिक माहितीसाठी, कृपया आमच्या तांत्रिक सेवा कार्यसंघाशी संपर्क साधा. खाली संपर्क माहिती पहा.

आमच्याशी संपर्क साधा

  • उत्तर अमेरिका - यूएसए, कॅनडा आणि कॅरिबियन
    • वॉरंटी फोन: +४९ ७११ ४०० ४०९९०
    • वॉरंटी फॅक्स: +४९ ७११ ४०० ४०९९०
    • वॉरंटी ईमेल: WarrantyInquiries@TrueMfg.com
    • तांत्रिक फोन: +४९ ७११ ४०० ४०९९०
    • तांत्रिक ईमेल: Service@TrueMfg.com
    • 7:00am-6:00pm CST सोमवार-शुक्रवार;
    • शनिवारी सकाळी 8:00 ते 12:00 दुपारी
  • मेक्सिको
  • लॅटिन अमेरिका
    • फोन: +८६ २१ ३३३९ २२१५/२१४५
    • ServiceLatAm@TrueMfg.com
    • सकाळी 9:00-5:30 MF
  • यूके, आयर्लंड, मध्य पूर्व, आफ्रिका आणि भारत
  • ऑस्ट्रेलिया
  • युरोपियन युनियन आणि स्वतंत्र राज्यांचे राष्ट्रकुल

BUILDING THE FINEST COMMERCIAL REFRIGERATION — True, “The Best of the Cold Ones”

वारंवार विचारले जाणारे प्रश्न

What should I do if the control locks after inactivity?

If the control locks after 60 seconds of inactivity, press any button to check the lock status. If it shows 'Loc,' press and hold the back button and up arrow until 'unL' appears.

How can I unlock the control?

To unlock the control, follow the steps mentioned in the 'Enter Password' section of the manual.